A710/IR2 dual infrared flame detector provide a new generation of fire detection capability and technical standards. It adopts two specially designed pieces of narrow-band infrared sensors, which can distinguish the real flame radiation and interference sources effectively and reduce the impact of environmental factors on detector extremely by means of the built-in 16-bit microprocessor and proprietary signal algorithm processing. With multiple sensitivity levels and output options, A710/IR2 can meet more application demands. 


1. Multistage sensitivity for more occasions

2. Excellent false alarm rejection

3. Automatic faults check and alarm

4. Multiple output options to meet different demands

5. Wide detection field

6. 360 degree adjustable universal mounting bracket

7. Particular flame identification technology

8. Explosion-proof design suitable for the hazardous locations of industrial site





Spectrum range                                               4.34.5 um

Operating voltage                                            24 VDC (operating range is 18 to 30 VDC)

Operating Current (only relay output)          25 mA maximum without alarm, 35 mA maximum with alarm

Operating Current (only current output)      30 mA maximum without alarm, 45 mA maximum with alarm

View angle                                                        90°

Sensitivity level                                                 multiple adjustable sensitivity levels 

Output                                                                3 output options: only relays, only current output, or both relays and output

Relays (optional)                                             a normally open contact for fire alarm and another normally closed contact for                                                                                     fault, both rated 2 A at 30 VDC

Current output (optional)                               15 mA at fire alarm state, 5 mA at normal state, <3 mA at fault state

Operating Temperature                                -0°C50°C

Operating Humidity                                        095RH.

Storage temperature                                     -40°C85°C.

Explosion proof level                                     EX dC T6 Gb/ tD A21 IP66 T80℃ 

Ingress protection                                          IP 66

Cable entry                                                      2×M20

Weight                                                              3 Kg

Enclosure material                                        Aluminum alloy, painted surfaces

Response time

Fuel

Size/Flow rateS

Average Response Time

gasoline

0.3×0.3 m

10 S

gasoline

0.7×0.7 m

5 S

Detection distance

Fuel

Size/Flow rateS

Distance

gasoline

0.3×0.3 m

40 m

methane

0.5×0.2 (H×W) m

30 m


 

Copyright Shanghai AEGIS industrial safety equipment co., LTD 2014 All Rights Reserved.